Aircore EC+ Fan Installation, Operation, and Maintenance Manual

Guides and Manuals

Read all safety instructions before you work on the Aircore EC+ Fan. Ignoring these precautions risks death, serious injury, or damage to the fan and its associated components.

Product
Aircore EC+ Fan
Document type
Guides and Manuals
Revised
Published
Format
PDF
Language
English (US)
Aircore EC+ Fan

 

Safety information


Read all safety instructions before you work on the Aircore EC+ Fan. Ignoring these precautions risks death, serious injury, or damage to the fan and its associated components.
 

Only qualified personnel may install and service Aircore EC+ Fans. Improper installation can cause electric shock, contact with moving parts, and other hazards that result in injury or death.

  • Follow all local electrical and safety codes, and where applicable, the National Electric Code (NEC) and the National Fire Protection Association (NFPA) standards.
  • Disconnect electrical power before you work on the unit, remove any guard, or open an access door.
  • Apply lockout/tagout procedures so that no one can energize the unit while you install or service it.
  • Route the power cable so that it cannot kink or contact oil, grease, hot surfaces, or chemicals.
  • Confirm the power source matches the electrical requirements of the equipment.
  • A turning rotor generates voltage at the motor terminals even when power is disconnected. Stop the impeller and secure it against rotation before you open any electrical compartment.
     

This manual uses the following safety messages.

Note: Indicates information that can aid in the completion of a process or step, or
practices not related to personal injury.

 

Table of Contents

Safety information 
Revision history 

  1. Introduction

    1.1 Purpose and scope

    1.2 Product overview

    1.3 Fan components

    1.4 Fan wheel and support structure

    1.4.1 Wheel balance

    1.5 Maximum RPM

     

  2. Receiving, handling, and storage

    2.1 Nameplate

    2.2 Catalog number decoder

    2.3 Fan weights

    2.4 Wheel alignment

    2.5 Shipping crates

    2.6 Removal from crate

    2.7 Storage

    2.7.1 Inspection and maintenance

    2.7.2 Rotation schedule and care

    2.8 Removal from storage 

     

  3. Fan installation

    3.1 Preparation

    3.1.1 Operating ambient temperature

    3.1.2 Altitude

    3.1.3 Ingress protection

    3.2 Mechanical installation

    3.2.1 Location

    3.2.2 Installation clearances

    3.2.3 Orientation

    3.2.4 Mounting

    3.3 Electrical installation

    3.3.1 Connection requirements

    3.3.2 Control methods

    3.3.3 Ground circuit verification

    3.3.4 Grounding configurations

    3.3.5 Connection locations

    3.3.6 Conductor size and terminal data

    3.3.7 Circuit breaker and wire sizing

    3.3.8 Aircore EC+ motor connections

    3.3.9 Aircore EC+ (AFE) motor connections

    3.3.10 Daisy-chain wiring

    3.3.11 LED operation

    3.4 Fan motor rotation

    3.5 Software control

     

  4. Piezometric airflow measurement

     

  5. Maintenance

    5.1 Windmilling during servicing

    5.2 Fan inspection and cleaning

    5.3 Bearing lubrication

    5.4 Taper-Lock bushing

    5.4.1 Tightening

    5.4.2 Loosening and realigning 
     

  6. Fan operations

    6.1 Windmilling during operation 
     

  7. Related documents

     

  8. Troubleshooting guide

    8.1 Motor troubleshooting

    8.2 Fan troubleshooting 
     

  9. Appendix

    Technical specifications 

 

 


 

1.  Introduction

This manual covers the Infinitum Aircore EC+ Fan. Read the safety information at the front of this manual before starting any procedure. Three hazards recur throughout and apply even when the fan is disconnected:

  • Airflow through the system can turn the wheel (windmilling)
  • Because the rotor uses permanent magnets, a turning wheel generates voltage at the motor terminals.
  • The drive’s capacitors hold a charge for one minute after power is removed.

Before any work in the fan section, secure the wheel against rotation and wait at least one minute after removing power.

Frame20-Aircore-Motor.png

 

1.1  Purpose and scope

This manual is intended for qualified personnel who install and service the Aircore EC+ fans. It covers safety precautions, receiving and storage, mechanical and electrical installation, operation, maintenance, Level-1 troubleshooting, and technical specifications.

Motor-level service, Modbus register detail, I-con software, and BACnet communication are outside the scope of this manual. For those topics, see the Aircore EC+ Installation, Operation, and Maintenance Manual and other documents listed in Section 8, Related documents.
 

1.2  Product overview

The Infinitum Aircore EC+ Fan is a centrifugal fan assembly consisting of an aluminum backward-curved fan wheel, a galvanized steel support structure, and an Aircore EC+ motor: an axial-flux motor and Variable Frequency Drive (VFD) integrated in one unit.

The motor uses an air-core design: the stator is a printed circuit board (PCB) rather than laminated iron with copper windings. This construction eliminates iron core losses and reduces motor weight compared with an equivalent iron-core induction motor, while delivering comparable power output.

The VFD provides variable speed control and maintains high efficiency across the fan’s full operating range, including at reduced speeds.

 

1.3  Fan components

 

1.4  Fan wheel and support structure

The Infinitum Aircore EC+ Fan wheel is an aluminum backward-curved centrifugal wheel with airfoil blades, optimized for use with Infinitum Aircore EC+ motors.

Viewed from the shaft end, the motor’s default rotation is counterclockwise (CCW). Infinitum programs each motor for the rotation its wheel requires: clockwise (CW) for EFxxxx01, EFxxxx02, and EFxxxx04 wheels, and counterclockwise (CCW) for EFxxxx03 wheels.

The supporting structure is galvanized steel. The fan is assembled with Wizlock ™ fasteners and Huck Magna-Lok™ for a robust, vibration-resistant design.

 

1.4.1  Wheel balance

Wheels dynamically balance quality grade G6.3 per AMCA/ANSI Standard 204 (Vibration and Balance Levels for Fans). System vibration is measured in three axes (horizontal, vertical, axial) prior to shipping to ensure vibration is within the tolerances for BV-3 mounted to a rigid structure per AMCA/ANSI standard 204.

Note: BV-4 balance and vibration levels are available as a paid option.

 

1.5  Maximum RPM

Aircore EC+ Fan units have a maximum RPM depending on the fan size. See Table 1 for details.

 


2.  Receiving, handling, and storage

Inspect the shipment for damage and shortages immediately upon receipt. Record any item discrepancy or apparent damage on the delivery receipt before signing it.

Concealed damage is damage found after the shipment is opened that was not evident from an external inspection. If you find concealed damage, request an inspection by the carrier immediately. Report it to the carrier within 15 days of delivery. Claims made after 15 days are rejected.
Move the crated fan assembly with a dolly, pallet jack, or fork truck.

 

2.1  Nameplate

  • Compare data on the fan nameplate in Figure 2 and the motor nameplate in Figure 3 with the purchase order to verify receipt of the proper Aircore EC+ Fan. Labels are on the motor shroud.
  • Confirm that the nameplate ratings match the available power supply and control equipment.

 

2.2  Catalog number decoder

Each Infinitum Aircore EC+ Fan and motor is identified by a catalog number that encodes its configuration. Figures 4 and 5 show how the decoder works.

 

2.3  Fan weights

Lifting equipment must support the fan assembly and account for the lift point angle. See Table 2 for fan assembly weights.

 

2.4  Wheel alignment

To maintain efficient fan performance, ensure the correct axial overlap between the impeller and inlet cone. Verify these values before initial start-up, after the first 24 hours of operation, and following any service. Refer to Tables 3 and 4 for the required overlap (u). Figures 6 and 7 show the location of the overlap.

 

2.5  Shipping crates

Aircore EC+ Fans are shipped individually in wooden crates.

 

2.6  Removal from crate

To remove the fan from the crate:

1. Remove the top of the crate.
2. Remove the fasteners securing the fan to the crate base.
3. Position the lifting device directly above the fan’s center of gravity so the fan
doesn’t swing when it clears the crate base.
4. Attach the straps to the fan frame at points shown in Figure 9.
5. Lift the fan vertically until it is clear of the crate.
6. Lower the fan onto a level surface and remove the straps.
7. Turn the impeller by hand to verify that it rotates freely without binding.
8. Verify the axial overlap between the impeller and the inlet cone. See section 2.4 Wheel alignment.

 

2.7  Storage

Fans are protected against damage during shipment. If they cannot be installed and put into operation immediately upon receipt, certain precautions are necessary to prevent deterioration during storage. The consignee is responsible for the integrity of fans and accessories during storage. Infinitum will not be responsible for damage during storage.

The ideal storage environment for fans and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Maintain temperatures between -40 °F (-40 °C) and 185 °F (85 °C) (wide temperature swings may cause condensation and “sweating” of metal parts). Cover windows to prevent temperature variations caused by sunlight and prevent UV exposure. Provide thermometers and humidity indicators at several points and maintain the atmosphere at 95% relative humidity, or lower.

Use trays of renewable desiccant or a portable dehumidifier if needed to remove moisture from the air in the storage enclosure.

Thermostatically controlled portable heaters (vented outdoors) may be required to maintain even temperatures inside the enclosure.

Store at least 3.5 in (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Provide aisles between parts and along all walls, to permit air circulation and space for inspection.

 

2.7.1  Inspection and maintenance

Inspect fans and accessories at least once per quarter, while in storage. Log results of inspection and maintenance performed. A typical log entry should include the following:

  1. Date
  2. Inspector’s Name
  3. Name of Fan
  4. Location
  5. Condition of paint or coating
  6. Moisture present
  7. Dirt accumulated
  8. Corrective steps taken

If moisture or dirt accumulations are found on parts, locate and eliminate the source.

 

2.7.2  Rotation schedule and care

While a fan is in storage, perform the following maintenance to protect the bearings and prevent corrosion.

 

2.7.2.1  Wheel rotation

Rotate the wheel every three months. Rotation redistributes grease in the bearings and reduces the risk of corrosion formation on rolling elements and raceways. Turning the wheel also turns the motor’s permanent magnet rotor, which generates voltage at the motor terminals.

  1. Leave the fan in its shipping crate.
  2. Turn the wheel by hand 10 to 15 full revolutions. Bearing seals may make the wheel slightly stiff to turn; this is normal.

 

2.7.2.2  Corrosion protection

During each quarterly rotation, inspect painted surfaces and machined parts for deterioration and rust.

  • Paint: If the paint is deteriorating on the motor shroud, touch up or repaint affected areas. For fans with special coatings, contact
    Infinitum for repair instructions.
  • Machined parts: If rust appears on parts coated with rust preventative, restore them promptly. Shafts and bearing collars are the most critical.
     

To remove rust:
Remove the original rust preventative coating with petroleum solvent and clean lint-free cloths.

  1. Polish off any remaining rust with crocus cloth or fine emery paper and oil. Remove only the rust. Do not scratch, pit, or remove base metal.
  2. Wipe the surfaces clean with lint-free cloths.
  3. Recoat surfaces evenly and thoroughly with rust preventative.

 

2.8  Removal from storage

As fans are removed from storage to be installed in their final location, they should be protected and maintained in similar fashion, until the fan equipment goes into operation. Before installing, check the fan for loose parts, debris, loose fasteners, or other parts that could become dangerous projectiles if not removed prior to start-up.

Notes:

  1. Failure to check and tighten all fasteners and set screws before starting the fan voids the warranty.
  2. Wheel alignment can shift during storage. Check the axial overlap against section 2.4 Wheel alignment, before start-up.

     


 

3.  Preparation

Review this entire manual prior to scheduling the Aircore EC+ Fan installation. All equipment related to systems operation must be secured and have an active lockout/tagout (LOTO) procedure in accordance with application specific safety policies. All users should be notified of equipment outage.

 

3.1.1  Operating ambient temperature

The ambient temperature of the air supplied to the motor cooling inlet should not exceed 104 °F (40 °C) or be less than -13 °F (-25 °C). Power derates by 2% per °C above 104 °F (40 °C) up to 122 °F (50 °C). Use the Infinitum Motor Selection Tool to confirm derating details.
Consult Infinitum for ambient temperatures not within these requirements.

Contact Infinitum before starting below -13 °F (-25 °C).

For continuous operation at ambient temperatures below -13 °F (-25 °C), special low temperature bearings are required. Contact Infinitum for any application below -13 °F (-25 °C) ambient.

 

3.1.2  Altitude

Infinitum fans are designed to operate at altitudes of 0 ft (0 m) to 2,000 ft (1,000 m). Power derates by 9% per 2,000 ft (1,000 m) when the motor operates between 2,000 ft (1,000 m) to 6,560 ft (2,000 m).

 

3.1.3  Ingress protection

The nameplate identifies the Infinitum motor’s Ingress Protection (IP) rating. To maintain this IP rating, use cable glands or seals at all
wiring ports, and keep all gaskets and covers in place.

 

3.2  Mechanical installation

This section covers location, installation clearance, orientation, and mounting for the Aircore EC+ Fan series.

 

3.2.1  Location

Aircore EC+ Fans have guidelines for the location and operating environment. These guidelines are listed below:

  • The Aircore EC+ Fan should be in a ventilated enclosure and should be in an area that allows air circulation.
  • Air cooling inlets and outlets must not be obstructed.
  • The enclosure cannot be in an area with harmful or explosive gases.
  • The area should be free from dust and metallic particles.
  • The motor should be easily accessed for cleaning and maintenance.

 

3.2.2  Installation clearances

Installing the Aircore EC+ Fan too close to other components reduces air performance. Peak performance is measured in a free-blowing open configuration.

Refer to Figure 10 for fan clearance dimensions, and to the Infinitum Fan Selection Tool or other design specifications for spacing between fans.

 

3.2.3  Orientation

Aircore EC+ Fans can be used in any orientation: horizontal, shaft up, or shaft down.

 

3.2.4  Mounting

Aircore EC+ Fans come with mounting holes in the side of the frame and the front faceplate (Figure 11). This facilitates mounting the fan assembly to a fan wall, fan array, or plenum using flanges, brackets or other attachment techniques. Infinitum does not recommend face mounting without using additional mounting points due to the increased potential for system level structural resonance. The customer must ensure the mounting structure is adequate to support the fans. Infinitum is not responsible for injury, damaged equipment, or poor fan performance caused by improper mounting/fan support.

Note: Mounting dimensions are subject to change. Coordinate with Infinitum prior to design.

 

Note: Values above are in millimeters (mm) and subject to change. Refer to CAD models for the latest designs.

 

3.3  Electrical installation

This section covers connection requirements, grounding, wiring guidelines, and control options for the Aircore EC+ Fan.

Sections 3.3.1 to 3.3.7 apply to both motor variants: Aircore EC+ and the Aircore EC+ with AFE. The control connections differ between variants and are covered in sections 3.3.8 and 3.3.9. If the motor catalog number starts with AE, go to section 3.3.8. If it starts with AM, go to section 3.3.9.

 

3.3.1  Connection requirements

Wire tensile forces can affect the point of termination during installation and motor operation. Terminal blocks with the correct wiring installed ensure safe motor operation. Using the correct wire gauge and amount of exposed conductor length with ferrules installed on each wire satisfies the requirements.

To install ferrules:

  1. Disconnect and lock out motor supply power.
  2. Stop the impeller and secure it against rotation.
  3. Wait at least one minute for capacitors to discharge.
  4. Verify voltage at the motor terminals with a properly tested voltage meter.
  5. Strip wires and crimp on wire ferrules.

Install each wire into the appropriate terminal block as provided in the wiring instructions. Verify all connections are tight and installed to specifications.

Follow NFPA 70 (NEC) and NEMA MG 2 for motor power wiring.

 

3.3.2  Control methods

Infinitum provides its own configuration software, called I-con motor control software (I-con), for configuring and controlling motors.
Infinitum Aircore EC+ motors support the following standard industry control methods:

  • Analog/Digital
  • Modbus RTU
  • BACnet MS/TP
  • Modbus TCP or Modbus RTU for I-con

Note: Refer to I-con for additional information on register configuration for the different modes.

 

3.3.2.1  Analog/Digital connection

Enable this mode by configuring, at a minimum, the registers for control mode, speed input source, and start/stop input source. Control speed with an analog signal (0-10 V, 4-20 mA) or with a combination of digital inputs. Contact Infinitum if Analog/Digital mode is required as a default. Note that, even when the control mode is set for Analog/Digital, the motor communicates over Modbus for all functions except for speed control. The Aircore EC+ motor requires a Modbus RTU server address, but the EIA-RS485 wiring to a Modbus RTU master is optional.

Refer to the Modbus Parameters Manual for additional details.

 

3.3.2.1.1  GUI override (I-con)

The user activates GUI override mode manually in I-con. It is not intended to be activated externally, for example from a controller. This mode enables I-con to temporarily override Analog/Digital speed control when the motor is configured for Analog/Digital control mode.

 

3.3.2.2  Modbus connection

Enable this mode by configuring, at a minimum, the registers for control mode, speed input source, and start/stop input source. Infinitum ships Aircore EC+ motors configured for Modbus by default. The Aircore EC+ motor requires a Modbus RTU server address and hardwired EIA-RS485 wiring to a Modbus RTU master.

Refer to the Modbus Parameters Manual for more details.

If BACnet MS/TP communication is utilized, the Aircore EC+ motor is configured for Modbus. The BACnet MS/TP module converts the Modbus RTU protocol to BACnet MS/TP. The Aircore EC+ motor, configured for BACnet MS/TP communication, requires a Modbus RTU server address.

Refer to the BACnet User Manual for more details.

 

3.3.3  Ground circuit verification

Take resistance readings with a multimeter on the ground motor circuit to verify continuity of the equipment grounding conductor back to the service ground. Per NEC 250.4(A)(5), the path must be low-impedance and capable of carrying fault current. Readings should be near zero (typically less than 1 Ω, or as your site standard requires). All electrical equipment must be grounded and bonded to the facility ground system with minimal resistance.

Never apply power to a motor that does not have a complete ground circuit. 

 

3.3.4  Grounding configurations

Infinitum Aircore EC+ motors can be installed in one of the
following:

  1. Grounded Wye
  2. Grounded Wye in combination with either Delta or High Resistance Ground (HRG) topology. The catalog ordering number identifies the grounding
    topology.

 

3.3.5  Connection locations

Each of the circuit boards and housing components has a separate design function. Only the Control Interface Module
(CIM) and AC Input have user inputs.
Figure 12 highlights the main circuit boards and connection points.

  1. Power board: Connections for three-phase supply. Rectifiers convert AC to DC for internal use on this board.
  2. Control interface module (CIM). This circuit board contains advanced controls and communications.
  3. AC Input: Grounding lug is in the chassis.

 

3.3.6  Conductor size and terminal data

Table 6 lists the maximum conductor size, exposed conductor length, and terminal type for each board and terminal.

3.3.7  Circuit breaker and wire sizing

Provide short-circuit protection for the input power conductors. Use UL- and/or CSA-approved Class CC or Class J fuses, or UL 489 circuit breakers, sized per applicable regulations or Table 7. Size the supply conductors to the motor’s current requirements. Table 8 lists the connector minimum and maximum wire sizes.

Overload protection is not required for Infinitum motors marked as Electronically Protected L or E.P.L. Use and set approved motor overload protectors as local regulations require (UL and/or CSA). Combination motor controllers, such as UL Type E controllers, when used as intended, may be used to provide disconnect, short circuit protection, and overload protection in the same device.

The maximum permissible short circuit current at the drive input power terminals is 5 kA.

Note: Confirm latest rated current values using the Motor Selection Tool.

 

3.3.8  Aircore EC+ motor connections

This section covers the control and power wiring for the Aircore EC+ motor. Before removing the VFD cover, disconnect and lock out power to all relay circuits; see warning in section 3.3.8.1. Remove the VFD cover for access to Analog/Digital, Modbus, and (optional) BACnet connections.

 

3.3.8.1  Control wiring requirements

Join shield wires with a wire nut. Do not connect shields to COM.

  • Control terminals use push-button spring clips.
  • The relay output indicates internal faults only; it cannot be configured.
  1. Relay (1) – NO / NC (KCOM must be used)
  • Max voltage: 250 VAC / 30 VDC
  • Max current: NO-5 A VAC, 5 A VDC
  • Max current: NC-3 A VAC or VDC
  1. Digital input accepts 24 VDC (4x) – DIN1, DIN2, DIN3, DIN4

      3. Digital output (2x) – DO1 & DO2

  • Open drain output
  • Max switching voltage: 40 VDC
    Max switching current: 350 mA

NOTICE: Permanent damage to DO1 and DO2 can result from exceeding 40 VDC or 350 mA.

  1. Auxiliary voltage (1) – +24V (COM must be used), 250 mA max
  2. Analog output (1) – A_OUT (COM must be used) 10 V, 10 mA
    max
  3. Analog input (1) – A_IN (COM must be used)
  4. EIA-485 interface (1) – 485_P & 485_N (Modbus RTU or BACnet
    MS/TP)
  5. EIA-485 termination switch. (Default is Off)
  6. RJ45 (Ethernet) for I-con connection
  7. Optional BACnet module
  8. USB-C for I-con connection

Note: Earlier versions of the CIM-CIO board use a USB-micro as a serial port to connect to I-con. The CIM-CIO board also supports a TCP port where an RJ45 cable can be used to connect to I-con.

 

 

3.3.8.2  Analog control wiring guidelines
To control the unit using Analog control, use the wiring guidelines on the CIM-CIO board (Figures 13 and 13a). Note that a 24 VDC external voltage source can be used for the IO, but it must have a common DC reference.

Refer to Analog / Digital Control Configuration and Wiring for additional details.

 

3.3.8.3  Modbus RTU or BACnet MS/TP wiring guidelines

To control the motor with Modbus RTU or BACnet MS/TP, use the wiring guidelines to connect to the Communication I/O.

  • On the last unit on a daisy-chain Modbus RTU or BACnet MS/TP configuration, set the EIA-485 termination DIP switch to “ON”. The termination resistance is 120 Ω.
  • On all other units set the DIP switch to “OFF”.
  • For Modbus RTU operation, change the server address in the motor configuration parameters. Refer to the Modbus Parameters Manual for required changes.
  • For BACnet MS/TP operation, change the Device Instance field to give each motor a unique BACnet identifier. Refer to the BACnet User Manual.
  • To connect multiple motors, see section 3.3.10, Daisy-chain wiring.

 

3.3.8.4  AC main input connections

The AC main inputs are on the power board (Figure 14).

The AC input terminals feature spring clips. Lower the orange tab, insert the wire, then close the tab to secure it (Aircore EC+ variant only). The grounding lug is located off the power board on the chassis itself.

Provide 415 V/460 V/575 VAC, three-phase, 60 Hz power to the unit at the AC main input connection points at the AC main input terminals. Make sure to install the ground connection.

The supply voltage connections are:

  1. Supply voltage phase A
  2. Supply voltage phase B
  3. Supply voltage phase C

 

3.3.9  Aircore EC+ (AFE) motor connections

This section covers the control wiring for the Aircore EC+ with AFE motor. Only the control wiring requirements differ from the Aircore EC+. For analog control wiring, Modbus RTU or BACnet MS/TP wiring, and AC main input connections see sections 3.3.8.2, 3.3.8.3, and 3.3.8.4.

Before removing the VFD cover, disconnect and lock out power to all relay circuits; see warning in section 3.3.8.1. Remove the VFD cover for access to Analog/Digital, Modbus, and (optional) BACnet connections.

 

3.3.9.1  Control wiring requirements

The relay output signals internal fault only and is not configurable.

  1. Relay (1) – NO / NC (KCOM must be used)
  • Max voltage: 125 VAC / 30 VDC
  • Max current: NO-5 A VAC, 5 A VDC
  • Max current: NC-3 A VAC or VDC
  1. Digital input accepts 24 VDC (4x) – DIN1, DIN2, DIN3, DIN4
  2. Digital output (2x) – DO1 & DO2
  • Open drain output
  • Max switching voltage: 40 VDC
  • Max switching current: 350 mA
    NOTICE: Permanent damage to DO1 and DO2 can result from
    exceeding 40 VDC or 350 mA.
  1. Auxiliary voltage (1) – +24V (COM must be used), 250 mA max
  2. Analog output (1) – A_OUT (COM must be used) 10 V, 10 mA max
  3. Analog input (1) – A_IN (COM must be used)
  4. EIA-485 interface (1) – (Modbus RTU or BACnet MS/TP)
  5. EIA-485 termination switch. (Default is Off)
  6. USB for BACnet module programming
  7. Header for optional BACnet module
  8. USB-C for I-con connection
  9. Chassis terminal block

Note: The CIM-CIO-AFE board has only one USB-C and does not support a TCP/IP port.

3.3.10  Daisy-chain wiring

You can daisy-chain multiple Aircore EC+ Fans, as shown in Figure 16.
Refer to PN# 23-05 | September 6, 2023 for more details.
 

3.3.11  LED operation

All Infinitum motors in Aircore EC+ Fans have three LEDs viewable on the outside of the VFD that indicate operational status (Figure 17):
Green: Normal operation; mains AC input is active
Yellow: Blinking “heartbeat”; inverter is operational
Red: Fault or important user notification

3.4  Fan motor rotation

This section covers testing the fan motor’s rotation and system operation when
the motor is under load.

If the motor has been tested, and the technician has verified motor rotation
prior to installation, the facility can elect to skip this test.

Prerequisites:

The motor is installed, aligned, and electrically connected
When looking at the shaft end of Infinitum motors, the standard rotation is counterclockwise (CCW).
To check the motor rotation:

  1. Review all installation instructions and all warnings before testing the motor.
  2. Connect AC power.
  3. Follow all safety precautions and energize the motor briefly to determine rotation. If the motor rotates opposite to the intended direction, switch the direction command using I-con.
  4. Disconnect AC power

 

3.5  Software control

Infinitum Aircore EC+ motors are shipped with factory default settings for maximum speed, control methods, and other values. To change your motor’s settings, download I-con.
Refer to section 3 of I-con for information on firmware updates.

 


 

4.  Piezometric airflow measurement 

Infinitum Aircore EC+ Fans include two pre-installed rivet nuts (Figure 18). For users requiring airflow measurements these rivet nuts can be used with “push-to-fit” tube attachment devices.

One rivet nut is installed in the face of the fan, the other in the throat of the inlet cone. Using these rivet nuts and requisite tubing, use a pressure transducer to measure the air pressure drop through the inlet cone. Airflow through the fan assembly can be calculated from this pressure differential.

The cubic feet per minute airflow of Infinitum Aircore EC+ Fans can be calculated with the following formula and data from Infinitum: Q = K √ ΔP where K comes from Table 9 and ΔP is the differential static pressure from the two taps installed in the Aircore EC+ Fan. Q is in CFM; ΔP in inches of water.

Figure 18: Rivet nuts

 

 


 

5.  Maintenance

No spare parts should be required during the first year of normal operation.

Regular servicing and visual examinations, performed at the suggested intervals, will help maintain the fan’s performance and prevent
potential issues.

 

5.1  Windmilling during servicing

Even when the power supply is locked out, fans may cause injury or damage if the impeller is subject to “windmilling” which is the turning of the impeller and drive components due to a draft in the system. To guard against this hazard, secure the impeller to restrict rotational movement in a powered-down condition.

 

5.2  Fan inspection and cleaning

Inspection frequency depends on the condition of the air passing through the fan. Regularly scheduled inspection of all fan parts establishes a good maintenance routine. When the air is clean, maintenance can be as infrequent as once a year. Regular maintenance should include inspection and cleaning of all fan parts to remove all grease and other foreign particles from the entire wheel surface including blades and front and back plates.

 

5.3  Bearing lubrication

Motor bearings are pre-lubricated and sealed. No additional lubrication is required.

 

5.4  Taper-Lock bushing

The fan wheel is mounted on the shaft with a Taper-Lock bushing. If the bushing loosens during operation, tighten it as described in section 5.4.1. If the fan wheel needs to be repositioned or realigned on the shaft, release the bushing as described in section 5.4.2, then tighten it as described in section 5.4.1.

5.4.1  Tightening

To tighten the bushing:

  1. Stop the fan and lock out all power. Block the wheel so it cannot rotate. Airflow through the fan can turn the wheel even when the motor is locked out.
  2. Open the access door to get access to the bushing.
  3. Remove the grease from the forcing bore (black circle in Figure 19). Clean dirt and debris from the bushing face and screw heads.
  4. Check the shaft, key and bushing for damage, such as scoring, fretting or a worn keyway. If you find damage do not retighten. Contact Infinitum support.
  5. Check that the wheel is in the correct position, with the inlet cone overlap as shown in Figure 6 and the wheel centered in the inlet cone. If it is not, loosen and reposition the wheel as described in 5.4.2.
  6. Tighten screws 1 and 2 alternately and evenly to the torque given in Table 10.
  7. Place a drift or sleeve against the bushing face and tap lightly with a hammer. Do not strike the bushing directly.
  8. Retighten screws 1 and 2 to the specified torque.
  9. Repeat steps 7 and 8 until the specified torque no longer turns the screws after hammering.
  10. Fill the forcing bore with grease to keep dirt out.
  11. Remove the blocking and turn the wheel by hand. Check that it does not rub on the inlet cone or housing.
  12. Close the access door and remove the lockout.
  13. Lock out power, block the wheel, and check that screws 1 and 2 are still at the Table 10 torque (steps 1-2 and 6) Restore the fan tonservice (steps 11-12).

 

5.4.2  Loosening and realigning

To loosen and realign the bushing:

  1. Stop the fan and lock out all power. Block the wheel so it cannot rotate. Airflow through the fan can turn the wheel even when the motor is locked out.
  2. Open the access door to get access to the bushing.
  3. Remove the grease from the forcing bore (black circle in Figure 19). Clean dirt and debris from the bushing face and screw heads.
  4. Support the wheel so it cannot drop or slide when the bushing releases.
  5. Remove screws 1 and 2. Replace any screw with damaged threads or head.
  6. Oil the threads of one screw and insert it into the forcing bore.
  7. Tighten the screw until the bushing releases from the hub.
  8. Remove the screw from the forcing bore.
  9. Move the wheel to the correct position on the shaft, with the inlet cone overlap as shown in Figures 6 and 7 and the wheel centered in the inlet cone.
  10. Make sure the tapered surfaces are clean. Do not lubricate them.
  11. Oil the threads and points of screws 1 and 2. Insert them into holes 1 and 2, but do not tighten them yet.
  12. Tighten the bushing as described in 5.4.1, starting at step 6.
     

     


 

6.  Fan operations

6.1 Windmilling during operation

Infinitum Aircore EC+ Fans can overcome windmilling (reverse rotation due to back pressure in HVAC applications) up to 200 RPM. In windmilling conditions under 200 RPM, the motor will stop the reverse rotation and resume operations in the required operational direction.

If the windmilling speed is above 200 RPM, alternative solutions are required such as anti-windmilling devices like brakes, clutches, or louvers.

 

 


 

7.  Related documents

The Aircore EC+ product family is supported by the following documentation.

 

  Aircore EC+
Installation, Operation,
and Maintenance Manual
Modbus
Parameters
Aircore EC+
I-con Software Manual
Aircore EC+
BACnet User Manual
Aircore EC+
Fan Installation, Operation,
and Maintenance Manual
Key Topics
Addressed
Receiving, installing,
operating,
maintaining the
motor; Level-1 motor
troubleshooting;
field wiring diagrams
and specifications.
Aircore EC+
Installation,
Operation, and
Maintenance
Table of supported
Modbus registers
with descriptions,
default values,
compatible
firmware versions,
and fault codes
for advanced
troubleshooting.
Modbus
Parameters
Installing, connecting
to, and navigating
the I-con software;
detailed description
of software features
and how they interact
with the hardware and
Modbus registers.
Aircore EC+ I-con
Software Manual
Supplemental for
installations using
the optional BACnet
module; BACnet-to-
Modbus mapping;
BACnet Protocol
Implementation
Conformance
Statement (PICS).
Aircore EC+ BACnet
User Manual
Receiving, installing,
operating, and
maintaining the
fan; Level-1 fan
troubleshooting; field
wiring diagrams and
specifications.
(This document)

The following resources help with fan selection and setup:

  • Infinitum Fan Selection Tool
  • Motor Selection Tool
  • Wiring Quick Start Guide

 

8.  Troubleshooting guide

These instructions do not cover all variations in equipment, nor do they provide information for every possible condition in installation, operation, or maintenance. For additional information, contact Infinitum Support.
Only qualified personnel with the proper tools and equipment should troubleshoot or service the motor. Follow LOTO procedures per company guidelines.

“Motor” refers to the motor system consisting of the motor and VFD.
When contacting Infinitum Support, have the Save State and Statistics file available for further diagnostics. Use I-con to save the Save State and Statistics files (Refer to the I-con Software Manual).

See Appendix A: Faults and error codes in the Modbus Parameters Manual for a list of fault codes.

See Appendix A: Faults and error codes in the Modbus Parameters Manual for a list of fault codes.


8.1  Motor troubleshooting

 

Note: Gen x refers to the motor generation.


8.2  Fan troubleshooting

*Always check motor amps and compare to nameplate rating. Excessive fan speed may overload the motor and result in motor failure.

Do not exceed the maximum fan RPM as provided in this manual.


9.  Appendix