Aircore EC+ Fan Installation, Operation, and Maintenance Manual
Read all safety instructions before you work on the Aircore EC+ Fan. Ignoring these precautions risks death, serious injury, or damage to the fan and its associated components.
Safety information
Read all safety instructions before you work on the Aircore EC+ Fan. Ignoring these precautions risks death, serious injury, or damage to the fan and its associated components.
Only qualified personnel may install and service Aircore EC+ Fans. Improper installation can cause electric shock, contact with moving parts, and other hazards that result in injury or death.
- Follow all local electrical and safety codes, and where applicable, the National Electric Code (NEC) and the National Fire Protection Association (NFPA) standards.
- Disconnect electrical power before you work on the unit, remove any guard, or open an access door.
- Apply lockout/tagout procedures so that no one can energize the unit while you install or service it.
- Route the power cable so that it cannot kink or contact oil, grease, hot surfaces, or chemicals.
- Confirm the power source matches the electrical requirements of the equipment.
- A turning rotor generates voltage at the motor terminals even when power is disconnected. Stop the impeller and secure it against rotation before you open any electrical compartment.
This manual uses the following safety messages.
Note: Indicates information that can aid in the completion of a process or step, or
practices not related to personal injury.
Table of Contents
Safety information
Revision history
-
Introduction
1.1 Purpose and scope
1.2 Product overview
1.3 Fan components
1.4 Fan wheel and support structure
1.4.1 Wheel balance
1.5 Maximum RPM
-
Receiving, handling, and storage
2.1 Nameplate
2.2 Catalog number decoder
2.3 Fan weights
2.4 Wheel alignment
2.5 Shipping crates
2.6 Removal from crate
2.7 Storage
2.7.1 Inspection and maintenance
2.7.2 Rotation schedule and care
2.8 Removal from storage
-
Fan installation
3.1 Preparation
3.1.1 Operating ambient temperature
3.1.2 Altitude
3.1.3 Ingress protection
3.2 Mechanical installation
3.2.1 Location
3.2.2 Installation clearances
3.2.3 Orientation
3.2.4 Mounting
3.3 Electrical installation
3.3.1 Connection requirements
3.3.2 Control methods
3.3.3 Ground circuit verification
3.3.4 Grounding configurations
3.3.5 Connection locations
3.3.6 Conductor size and terminal data
3.3.7 Circuit breaker and wire sizing
3.3.8 Aircore EC+ motor connections
3.3.9 Aircore EC+ (AFE) motor connections
3.3.10 Daisy-chain wiring
3.3.11 LED operation
3.4 Fan motor rotation
3.5 Software control
-
Piezometric airflow measurement
-
Maintenance
5.1 Windmilling during servicing
5.2 Fan inspection and cleaning
5.3 Bearing lubrication
5.4 Taper-Lock bushing
5.4.1 Tightening
5.4.2 Loosening and realigning
-
Fan operations
6.1 Windmilling during operation
-
Related documents
-
Troubleshooting guide
8.1 Motor troubleshooting
8.2 Fan troubleshooting
-
Appendix
Technical specifications
1. Introduction
|
This manual covers the Infinitum Aircore EC+ Fan. Read the safety information at the front of this manual before starting any procedure. Three hazards recur throughout and apply even when the fan is disconnected:
Before any work in the fan section, secure the wheel against rotation and wait at least one minute after removing power. |
1.1 Purpose and scope
This manual is intended for qualified personnel who install and service the Aircore EC+ fans. It covers safety precautions, receiving and storage, mechanical and electrical installation, operation, maintenance, Level-1 troubleshooting, and technical specifications.
Motor-level service, Modbus register detail, I-con software, and BACnet communication are outside the scope of this manual. For those topics, see the Aircore EC+ Installation, Operation, and Maintenance Manual and other documents listed in Section 8, Related documents.
1.2 Product overview
The Infinitum Aircore EC+ Fan is a centrifugal fan assembly consisting of an aluminum backward-curved fan wheel, a galvanized steel support structure, and an Aircore EC+ motor: an axial-flux motor and Variable Frequency Drive (VFD) integrated in one unit.
The motor uses an air-core design: the stator is a printed circuit board (PCB) rather than laminated iron with copper windings. This construction eliminates iron core losses and reduces motor weight compared with an equivalent iron-core induction motor, while delivering comparable power output.
The VFD provides variable speed control and maintains high efficiency across the fan’s full operating range, including at reduced speeds.
1.3 Fan components
1.4 Fan wheel and support structure
|
The Infinitum Aircore EC+ Fan wheel is an aluminum backward-curved centrifugal wheel with airfoil blades, optimized for use with Infinitum Aircore EC+ motors. Viewed from the shaft end, the motor’s default rotation is counterclockwise (CCW). Infinitum programs each motor for the rotation its wheel requires: clockwise (CW) for EFxxxx01, EFxxxx02, and EFxxxx04 wheels, and counterclockwise (CCW) for EFxxxx03 wheels. The supporting structure is galvanized steel. The fan is assembled with Wizlock ™ fasteners and Huck Magna-Lok™ for a robust, vibration-resistant design. |
1.4.1 Wheel balance
Wheels dynamically balance quality grade G6.3 per AMCA/ANSI Standard 204 (Vibration and Balance Levels for Fans). System vibration is measured in three axes (horizontal, vertical, axial) prior to shipping to ensure vibration is within the tolerances for BV-3 mounted to a rigid structure per AMCA/ANSI standard 204.
Note: BV-4 balance and vibration levels are available as a paid option.
1.5 Maximum RPM
Aircore EC+ Fan units have a maximum RPM depending on the fan size. See Table 1 for details.
2. Receiving, handling, and storage
Inspect the shipment for damage and shortages immediately upon receipt. Record any item discrepancy or apparent damage on the delivery receipt before signing it.
Concealed damage is damage found after the shipment is opened that was not evident from an external inspection. If you find concealed damage, request an inspection by the carrier immediately. Report it to the carrier within 15 days of delivery. Claims made after 15 days are rejected.
Move the crated fan assembly with a dolly, pallet jack, or fork truck.
2.1 Nameplate
- Compare data on the fan nameplate in Figure 2 and the motor nameplate in Figure 3 with the purchase order to verify receipt of the proper Aircore EC+ Fan. Labels are on the motor shroud.
- Confirm that the nameplate ratings match the available power supply and control equipment.
2.2 Catalog number decoder
Each Infinitum Aircore EC+ Fan and motor is identified by a catalog number that encodes its configuration. Figures 4 and 5 show how the decoder works.
2.3 Fan weights
Lifting equipment must support the fan assembly and account for the lift point angle. See Table 2 for fan assembly weights.
2.4 Wheel alignment
To maintain efficient fan performance, ensure the correct axial overlap between the impeller and inlet cone. Verify these values before initial start-up, after the first 24 hours of operation, and following any service. Refer to Tables 3 and 4 for the required overlap (u). Figures 6 and 7 show the location of the overlap.
2.5 Shipping crates
Aircore EC+ Fans are shipped individually in wooden crates.
2.6 Removal from crate
|
To remove the fan from the crate: 1. Remove the top of the crate. |
2.7 Storage
Fans are protected against damage during shipment. If they cannot be installed and put into operation immediately upon receipt, certain precautions are necessary to prevent deterioration during storage. The consignee is responsible for the integrity of fans and accessories during storage. Infinitum will not be responsible for damage during storage.
The ideal storage environment for fans and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Maintain temperatures between -40 °F (-40 °C) and 185 °F (85 °C) (wide temperature swings may cause condensation and “sweating” of metal parts). Cover windows to prevent temperature variations caused by sunlight and prevent UV exposure. Provide thermometers and humidity indicators at several points and maintain the atmosphere at 95% relative humidity, or lower.
Use trays of renewable desiccant or a portable dehumidifier if needed to remove moisture from the air in the storage enclosure.
Thermostatically controlled portable heaters (vented outdoors) may be required to maintain even temperatures inside the enclosure.
Store at least 3.5 in (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Provide aisles between parts and along all walls, to permit air circulation and space for inspection.
2.7.1 Inspection and maintenance
Inspect fans and accessories at least once per quarter, while in storage. Log results of inspection and maintenance performed. A typical log entry should include the following:
- Date
- Inspector’s Name
- Name of Fan
- Location
- Condition of paint or coating
- Moisture present
- Dirt accumulated
- Corrective steps taken
If moisture or dirt accumulations are found on parts, locate and eliminate the source.
2.7.2 Rotation schedule and care
While a fan is in storage, perform the following maintenance to protect the bearings and prevent corrosion.
2.7.2.1 Wheel rotation
Rotate the wheel every three months. Rotation redistributes grease in the bearings and reduces the risk of corrosion formation on rolling elements and raceways. Turning the wheel also turns the motor’s permanent magnet rotor, which generates voltage at the motor terminals.
- Leave the fan in its shipping crate.
- Turn the wheel by hand 10 to 15 full revolutions. Bearing seals may make the wheel slightly stiff to turn; this is normal.
2.7.2.2 Corrosion protection
During each quarterly rotation, inspect painted surfaces and machined parts for deterioration and rust.
-
Paint: If the paint is deteriorating on the motor shroud, touch up or repaint affected areas. For fans with special coatings, contact
Infinitum for repair instructions. -
Machined parts: If rust appears on parts coated with rust preventative, restore them promptly. Shafts and bearing collars are the most critical.
To remove rust:
Remove the original rust preventative coating with petroleum solvent and clean lint-free cloths.
- Polish off any remaining rust with crocus cloth or fine emery paper and oil. Remove only the rust. Do not scratch, pit, or remove base metal.
- Wipe the surfaces clean with lint-free cloths.
- Recoat surfaces evenly and thoroughly with rust preventative.
2.8 Removal from storage
As fans are removed from storage to be installed in their final location, they should be protected and maintained in similar fashion, until the fan equipment goes into operation. Before installing, check the fan for loose parts, debris, loose fasteners, or other parts that could become dangerous projectiles if not removed prior to start-up.
Notes:
- Failure to check and tighten all fasteners and set screws before starting the fan voids the warranty.
-
Wheel alignment can shift during storage. Check the axial overlap against section 2.4 Wheel alignment, before start-up.
3. Preparation
Review this entire manual prior to scheduling the Aircore EC+ Fan installation. All equipment related to systems operation must be secured and have an active lockout/tagout (LOTO) procedure in accordance with application specific safety policies. All users should be notified of equipment outage.
3.1.1 Operating ambient temperature
The ambient temperature of the air supplied to the motor cooling inlet should not exceed 104 °F (40 °C) or be less than -13 °F (-25 °C). Power derates by 2% per °C above 104 °F (40 °C) up to 122 °F (50 °C). Use the Infinitum Motor Selection Tool to confirm derating details.
Consult Infinitum for ambient temperatures not within these requirements.
Contact Infinitum before starting below -13 °F (-25 °C).
For continuous operation at ambient temperatures below -13 °F (-25 °C), special low temperature bearings are required. Contact Infinitum for any application below -13 °F (-25 °C) ambient.
3.1.2 Altitude
Infinitum fans are designed to operate at altitudes of 0 ft (0 m) to 2,000 ft (1,000 m). Power derates by 9% per 2,000 ft (1,000 m) when the motor operates between 2,000 ft (1,000 m) to 6,560 ft (2,000 m).
3.1.3 Ingress protection
The nameplate identifies the Infinitum motor’s Ingress Protection (IP) rating. To maintain this IP rating, use cable glands or seals at all
wiring ports, and keep all gaskets and covers in place.
3.2 Mechanical installation
This section covers location, installation clearance, orientation, and mounting for the Aircore EC+ Fan series.
3.2.1 Location
Aircore EC+ Fans have guidelines for the location and operating environment. These guidelines are listed below:
- The Aircore EC+ Fan should be in a ventilated enclosure and should be in an area that allows air circulation.
- Air cooling inlets and outlets must not be obstructed.
- The enclosure cannot be in an area with harmful or explosive gases.
- The area should be free from dust and metallic particles.
- The motor should be easily accessed for cleaning and maintenance.
3.2.2 Installation clearances
Installing the Aircore EC+ Fan too close to other components reduces air performance. Peak performance is measured in a free-blowing open configuration.
Refer to Figure 10 for fan clearance dimensions, and to the Infinitum Fan Selection Tool or other design specifications for spacing between fans.
3.2.3 Orientation
Aircore EC+ Fans can be used in any orientation: horizontal, shaft up, or shaft down.
3.2.4 Mounting
Aircore EC+ Fans come with mounting holes in the side of the frame and the front faceplate (Figure 11). This facilitates mounting the fan assembly to a fan wall, fan array, or plenum using flanges, brackets or other attachment techniques. Infinitum does not recommend face mounting without using additional mounting points due to the increased potential for system level structural resonance. The customer must ensure the mounting structure is adequate to support the fans. Infinitum is not responsible for injury, damaged equipment, or poor fan performance caused by improper mounting/fan support.
Note: Mounting dimensions are subject to change. Coordinate with Infinitum prior to design.
Note: Values above are in millimeters (mm) and subject to change. Refer to CAD models for the latest designs.
3.3 Electrical installation
This section covers connection requirements, grounding, wiring guidelines, and control options for the Aircore EC+ Fan.
Sections 3.3.1 to 3.3.7 apply to both motor variants: Aircore EC+ and the Aircore EC+ with AFE. The control connections differ between variants and are covered in sections 3.3.8 and 3.3.9. If the motor catalog number starts with AE, go to section 3.3.8. If it starts with AM, go to section 3.3.9.
3.3.1 Connection requirements
Wire tensile forces can affect the point of termination during installation and motor operation. Terminal blocks with the correct wiring installed ensure safe motor operation. Using the correct wire gauge and amount of exposed conductor length with ferrules installed on each wire satisfies the requirements.
To install ferrules:
- Disconnect and lock out motor supply power.
- Stop the impeller and secure it against rotation.
- Wait at least one minute for capacitors to discharge.
- Verify voltage at the motor terminals with a properly tested voltage meter.
- Strip wires and crimp on wire ferrules.
Install each wire into the appropriate terminal block as provided in the wiring instructions. Verify all connections are tight and installed to specifications.
Follow NFPA 70 (NEC) and NEMA MG 2 for motor power wiring.
3.3.2 Control methods
Infinitum provides its own configuration software, called I-con motor control software (I-con), for configuring and controlling motors.
Infinitum Aircore EC+ motors support the following standard industry control methods:
- Analog/Digital
- Modbus RTU
- BACnet MS/TP
- Modbus TCP or Modbus RTU for I-con
Note: Refer to I-con for additional information on register configuration for the different modes.
3.3.2.1 Analog/Digital connection
Enable this mode by configuring, at a minimum, the registers for control mode, speed input source, and start/stop input source. Control speed with an analog signal (0-10 V, 4-20 mA) or with a combination of digital inputs. Contact Infinitum if Analog/Digital mode is required as a default. Note that, even when the control mode is set for Analog/Digital, the motor communicates over Modbus for all functions except for speed control. The Aircore EC+ motor requires a Modbus RTU server address, but the EIA-RS485 wiring to a Modbus RTU master is optional.
Refer to the Modbus Parameters Manual for additional details.
3.3.2.1.1 GUI override (I-con)
The user activates GUI override mode manually in I-con. It is not intended to be activated externally, for example from a controller. This mode enables I-con to temporarily override Analog/Digital speed control when the motor is configured for Analog/Digital control mode.
3.3.2.2 Modbus connection
Enable this mode by configuring, at a minimum, the registers for control mode, speed input source, and start/stop input source. Infinitum ships Aircore EC+ motors configured for Modbus by default. The Aircore EC+ motor requires a Modbus RTU server address and hardwired EIA-RS485 wiring to a Modbus RTU master.
Refer to the Modbus Parameters Manual for more details.
If BACnet MS/TP communication is utilized, the Aircore EC+ motor is configured for Modbus. The BACnet MS/TP module converts the Modbus RTU protocol to BACnet MS/TP. The Aircore EC+ motor, configured for BACnet MS/TP communication, requires a Modbus RTU server address.
Refer to the BACnet User Manual for more details.
3.3.3 Ground circuit verification
Take resistance readings with a multimeter on the ground motor circuit to verify continuity of the equipment grounding conductor back to the service ground. Per NEC 250.4(A)(5), the path must be low-impedance and capable of carrying fault current. Readings should be near zero (typically less than 1 Ω, or as your site standard requires). All electrical equipment must be grounded and bonded to the facility ground system with minimal resistance.
Never apply power to a motor that does not have a complete ground circuit.
3.3.4 Grounding configurations
|
Infinitum Aircore EC+ motors can be installed in one of the
3.3.5 Connection locationsEach of the circuit boards and housing components has a separate design function. Only the Control Interface Module
|
3.3.6 Conductor size and terminal data
Table 6 lists the maximum conductor size, exposed conductor length, and terminal type for each board and terminal.
3.3.7 Circuit breaker and wire sizing
Provide short-circuit protection for the input power conductors. Use UL- and/or CSA-approved Class CC or Class J fuses, or UL 489 circuit breakers, sized per applicable regulations or Table 7. Size the supply conductors to the motor’s current requirements. Table 8 lists the connector minimum and maximum wire sizes.
Overload protection is not required for Infinitum motors marked as Electronically Protected L or E.P.L. Use and set approved motor overload protectors as local regulations require (UL and/or CSA). Combination motor controllers, such as UL Type E controllers, when used as intended, may be used to provide disconnect, short circuit protection, and overload protection in the same device.
The maximum permissible short circuit current at the drive input power terminals is 5 kA.
Note: Confirm latest rated current values using the Motor Selection Tool.
3.3.8 Aircore EC+ motor connections
This section covers the control and power wiring for the Aircore EC+ motor. Before removing the VFD cover, disconnect and lock out power to all relay circuits; see warning in section 3.3.8.1. Remove the VFD cover for access to Analog/Digital, Modbus, and (optional) BACnet connections.
3.3.8.1 Control wiring requirements
Join shield wires with a wire nut. Do not connect shields to COM.
- Control terminals use push-button spring clips.
- The relay output indicates internal faults only; it cannot be configured.
3. Digital output (2x) – DO1 & DO2
NOTICE: Permanent damage to DO1 and DO2 can result from exceeding 40 VDC or 350 mA.
Note: Earlier versions of the CIM-CIO board use a USB-micro as a serial port to connect to I-con. The CIM-CIO board also supports a TCP port where an RJ45 cable can be used to connect to I-con. |
|
3.3.8.2 Analog control wiring guidelinesTo control the unit using Analog control, use the wiring guidelines on the CIM-CIO board (Figures 13 and 13a). Note that a 24 VDC external voltage source can be used for the IO, but it must have a common DC reference.
Refer to Analog / Digital Control Configuration and Wiring for additional details.
3.3.8.3 Modbus RTU or BACnet MS/TP wiring guidelines
|
To control the motor with Modbus RTU or BACnet MS/TP, use the wiring guidelines to connect to the Communication I/O.
|
3.3.8.4 AC main input connections
|
The AC main inputs are on the power board (Figure 14). The AC input terminals feature spring clips. Lower the orange tab, insert the wire, then close the tab to secure it (Aircore EC+ variant only). The grounding lug is located off the power board on the chassis itself. Provide 415 V/460 V/575 VAC, three-phase, 60 Hz power to the unit at the AC main input connection points at the AC main input terminals. Make sure to install the ground connection. The supply voltage connections are:
|
|
3.3.9 Aircore EC+ (AFE) motor connections
This section covers the control wiring for the Aircore EC+ with AFE motor. Only the control wiring requirements differ from the Aircore EC+. For analog control wiring, Modbus RTU or BACnet MS/TP wiring, and AC main input connections see sections 3.3.8.2, 3.3.8.3, and 3.3.8.4.
Before removing the VFD cover, disconnect and lock out power to all relay circuits; see warning in section 3.3.8.1. Remove the VFD cover for access to Analog/Digital, Modbus, and (optional) BACnet connections.
3.3.9.1 Control wiring requirements
|
The relay output signals internal fault only and is not configurable.
Note: The CIM-CIO-AFE board has only one USB-C and does not support a TCP/IP port. |
3.3.10 Daisy-chain wiring
You can daisy-chain multiple Aircore EC+ Fans, as shown in Figure 16.
Refer to PN# 23-05 | September 6, 2023 for more details.
3.3.11 LED operation
|
All Infinitum motors in Aircore EC+ Fans have three LEDs viewable on the outside of the VFD that indicate operational status (Figure 17): Green: Normal operation; mains AC input is active Yellow: Blinking “heartbeat”; inverter is operational Red: Fault or important user notification |
3.4 Fan motor rotation
This section covers testing the fan motor’s rotation and system operation when
the motor is under load.
If the motor has been tested, and the technician has verified motor rotation
prior to installation, the facility can elect to skip this test.
Prerequisites:
The motor is installed, aligned, and electrically connected
When looking at the shaft end of Infinitum motors, the standard rotation is counterclockwise (CCW).
To check the motor rotation:
- Review all installation instructions and all warnings before testing the motor.
- Connect AC power.
- Follow all safety precautions and energize the motor briefly to determine rotation. If the motor rotates opposite to the intended direction, switch the direction command using I-con.
- Disconnect AC power
3.5 Software control
Infinitum Aircore EC+ motors are shipped with factory default settings for maximum speed, control methods, and other values. To change your motor’s settings, download I-con.
Refer to section 3 of I-con for information on firmware updates.
4. Piezometric airflow measurement
|
Infinitum Aircore EC+ Fans include two pre-installed rivet nuts (Figure 18). For users requiring airflow measurements these rivet nuts can be used with “push-to-fit” tube attachment devices. One rivet nut is installed in the face of the fan, the other in the throat of the inlet cone. Using these rivet nuts and requisite tubing, use a pressure transducer to measure the air pressure drop through the inlet cone. Airflow through the fan assembly can be calculated from this pressure differential. The cubic feet per minute airflow of Infinitum Aircore EC+ Fans can be calculated with the following formula and data from Infinitum: Q = K √ ΔP where K comes from Table 9 and ΔP is the differential static pressure from the two taps installed in the Aircore EC+ Fan. Q is in CFM; ΔP in inches of water. |
Figure 18: Rivet nuts |
5. Maintenance
No spare parts should be required during the first year of normal operation.
Regular servicing and visual examinations, performed at the suggested intervals, will help maintain the fan’s performance and prevent
potential issues.
5.1 Windmilling during servicing
Even when the power supply is locked out, fans may cause injury or damage if the impeller is subject to “windmilling” which is the turning of the impeller and drive components due to a draft in the system. To guard against this hazard, secure the impeller to restrict rotational movement in a powered-down condition.
5.2 Fan inspection and cleaning
Inspection frequency depends on the condition of the air passing through the fan. Regularly scheduled inspection of all fan parts establishes a good maintenance routine. When the air is clean, maintenance can be as infrequent as once a year. Regular maintenance should include inspection and cleaning of all fan parts to remove all grease and other foreign particles from the entire wheel surface including blades and front and back plates.
5.3 Bearing lubrication
Motor bearings are pre-lubricated and sealed. No additional lubrication is required.
5.4 Taper-Lock bushing
The fan wheel is mounted on the shaft with a Taper-Lock bushing. If the bushing loosens during operation, tighten it as described in section 5.4.1. If the fan wheel needs to be repositioned or realigned on the shaft, release the bushing as described in section 5.4.2, then tighten it as described in section 5.4.1.
5.4.1 Tightening
To tighten the bushing:
- Stop the fan and lock out all power. Block the wheel so it cannot rotate. Airflow through the fan can turn the wheel even when the motor is locked out.
- Open the access door to get access to the bushing.
- Remove the grease from the forcing bore (black circle in Figure 19). Clean dirt and debris from the bushing face and screw heads.
- Check the shaft, key and bushing for damage, such as scoring, fretting or a worn keyway. If you find damage do not retighten. Contact Infinitum support.
- Check that the wheel is in the correct position, with the inlet cone overlap as shown in Figure 6 and the wheel centered in the inlet cone. If it is not, loosen and reposition the wheel as described in 5.4.2.
- Tighten screws 1 and 2 alternately and evenly to the torque given in Table 10.
- Place a drift or sleeve against the bushing face and tap lightly with a hammer. Do not strike the bushing directly.
- Retighten screws 1 and 2 to the specified torque.
- Repeat steps 7 and 8 until the specified torque no longer turns the screws after hammering.
- Fill the forcing bore with grease to keep dirt out.
- Remove the blocking and turn the wheel by hand. Check that it does not rub on the inlet cone or housing.
- Close the access door and remove the lockout.
- Lock out power, block the wheel, and check that screws 1 and 2 are still at the Table 10 torque (steps 1-2 and 6) Restore the fan tonservice (steps 11-12).
5.4.2 Loosening and realigning
To loosen and realign the bushing:
- Stop the fan and lock out all power. Block the wheel so it cannot rotate. Airflow through the fan can turn the wheel even when the motor is locked out.
- Open the access door to get access to the bushing.
- Remove the grease from the forcing bore (black circle in Figure 19). Clean dirt and debris from the bushing face and screw heads.
- Support the wheel so it cannot drop or slide when the bushing releases.
- Remove screws 1 and 2. Replace any screw with damaged threads or head.
- Oil the threads of one screw and insert it into the forcing bore.
- Tighten the screw until the bushing releases from the hub.
- Remove the screw from the forcing bore.
- Move the wheel to the correct position on the shaft, with the inlet cone overlap as shown in Figures 6 and 7 and the wheel centered in the inlet cone.
- Make sure the tapered surfaces are clean. Do not lubricate them.
- Oil the threads and points of screws 1 and 2. Insert them into holes 1 and 2, but do not tighten them yet.
-
Tighten the bushing as described in 5.4.1, starting at step 6.
6. Fan operations
6.1 Windmilling during operation
Infinitum Aircore EC+ Fans can overcome windmilling (reverse rotation due to back pressure in HVAC applications) up to 200 RPM. In windmilling conditions under 200 RPM, the motor will stop the reverse rotation and resume operations in the required operational direction.
If the windmilling speed is above 200 RPM, alternative solutions are required such as anti-windmilling devices like brakes, clutches, or louvers.
7. Related documents
The Aircore EC+ product family is supported by the following documentation.
|
Aircore EC+ Installation, Operation, and Maintenance Manual |
Modbus Parameters |
Aircore EC+ I-con Software Manual |
Aircore EC+ BACnet User Manual |
Aircore EC+ Fan Installation, Operation, and Maintenance Manual |
|
|
Key Topics Addressed |
Receiving, installing, operating, maintaining the motor; Level-1 motor troubleshooting; field wiring diagrams and specifications. Aircore EC+ Installation, Operation, and Maintenance |
Table of supported Modbus registers with descriptions, default values, compatible firmware versions, and fault codes for advanced troubleshooting. Modbus Parameters |
Installing, connecting to, and navigating the I-con software; detailed description of software features and how they interact with the hardware and Modbus registers. Aircore EC+ I-con Software Manual |
Supplemental for installations using the optional BACnet module; BACnet-to- Modbus mapping; BACnet Protocol Implementation Conformance Statement (PICS). Aircore EC+ BACnet User Manual |
Receiving, installing, operating, and maintaining the fan; Level-1 fan troubleshooting; field wiring diagrams and specifications. (This document) |
The following resources help with fan selection and setup:
- Infinitum Fan Selection Tool
- Motor Selection Tool
- Wiring Quick Start Guide
8. Troubleshooting guide
These instructions do not cover all variations in equipment, nor do they provide information for every possible condition in installation, operation, or maintenance. For additional information, contact Infinitum Support.
Only qualified personnel with the proper tools and equipment should troubleshoot or service the motor. Follow LOTO procedures per company guidelines.
“Motor” refers to the motor system consisting of the motor and VFD.
When contacting Infinitum Support, have the Save State and Statistics file available for further diagnostics. Use I-con to save the Save State and Statistics files (Refer to the I-con Software Manual).
See Appendix A: Faults and error codes in the Modbus Parameters Manual for a list of fault codes.
See Appendix A: Faults and error codes in the Modbus Parameters Manual for a list of fault codes.
8.1 Motor troubleshooting
Note: Gen x refers to the motor generation.
8.2 Fan troubleshooting
*Always check motor amps and compare to nameplate rating. Excessive fan speed may overload the motor and result in motor failure.
Do not exceed the maximum fan RPM as provided in this manual.